Rockwell Automation Publication 1426-UM001F-EN-P - November 2013 267
PowerMonitor 5000 Unit Data Tables Appendix A
5 Int16 Logic Level 1
Gate 2 Function
Selects the logic type
0 = disabled
1 = AND
2 = NAND
3 = OR
4 = NOR
5 = XOR
6 = XNOR
IMPORTANT: XOR and XNOR use Inputs 1 and 2 only.
006
6 Int16 L1_G2 Input 1 Selects the first input parameter for the gate. Each gate has four inputs.
0 = Disabled
1 = Setpoint 1
2 = Setpoint 2
3 = Setpoint 3
20 = Setpoint 20
IMPORTANT: Negative numbers invert the input.
0 -20…20
7 Int16 L1_G2 Input 2 Selects the second input parameter for the gate. Each gate has four inputs.
0 = Disabled
1 = Setpoint 1
2 = Setpoint 2
3 = Setpoint 3
20 = Setpoint 20
IMPORTANT: Negative numbers invert the input.
0 -20…20
8 Int16 L1_G2 Input 3 Selects the third input parameter for the gate. Each gate has four inputs.
0 = Disabled
1 = Setpoint 1
2 = Setpoint 2
3 = Setpoint 3
20 = Setpoint 20
IMPORTANT: Negative numbers invert the input.
0 -20…20
9 Int16 L1_G2 Input 4 Selects the fourth input parameter for the gate. Each gate has four inputs.
0 = Disabled
1 = Setpoint 1
2 = Setpoint 2
3 = Setpoint 3
20 = Setpoint 20
IMPORTANT: Negative numbers invert the input.
0 -20…20
10 Int16 Logic Level 1
Gate 3 Function
Selects the logic type
0 = disabled
1 = AND
2 = NAND
3 = OR
4 = NOR
5 = XOR
6 = XNOR
IMPORTANT: XOR and XNOR use Inputs 1 and 2 only.
006
Table 70 - Configuration.Setpoint_Logic Data Table
Element
Number
Type Tag Name Description Default Range