Manual
Rockwell Automation Publication 1426-UM001F-EN-P - November 2013 261
PowerMonitor 5000 Unit Data Tables Appendix A
13 Real Hysteresis 12 The value in magnitude or percent of reference at which the output action is deasserted.
Example: A less than condition deasserts at (threshold + hysteresis), a greater than condition
deasserts at (threshold - hysteresis).
0 0…10,000,000
14 Real Assert Delay
Seconds 12
The amount of time to delay the output action after a setpoint trigger occurs. Minimum equals
realtime update rate setting.
0 0.000…3600
15 Real Deassert Delay
Seconds 12
The amount of time to delay deassertion after the setpoint trigger releases. Minimum equals
realtime update rate setting.
0 0.000…3600
16 Real Parameter
Selection 13
Selection of the input parameter from the Setpoint Parameter Selection List
. 0 0…105
17 Real Input Reference
Selection 13
Selects the type of input conditioning for non boolean parameters.
0 = Absolute Value
00
18 Real Test Condition 13 0 = Disabled
1 = Less Than
2 = Greater Than
3 = Equals
0 0…3
19 Real Evaluation Type
13
0 = Magnitude
1 = State
2 = Percent of Reference (not supported in the M5 model)
3 = Percent of Sliding Reference (not supported in the M5 model)
00…3
20 Real Threshold 13 The value, percent, or state that triggers the output action. 0 -10,000,000…
10,000,000
21 Real Hysteresis 13 The value in magnitude or percent of reference at which the output action is deasserted.
Example: A less than condition deasserts at (threshold + hysteresis), a greater than condition
deasserts at (threshold - hysteresis).
0 0…10,000,000
22 Real Assert Delay
Seconds 13
The amount of time to delay the output action after a setpoint trigger occurs. Minimum equals
realtime update rate setting.
0 0.000…3600
23 Real Deassert Delay
Seconds 13
The amount of time to delay deassertion after the setpoint trigger releases. Minimum equals
realtime update rate setting.
0 0.000…3600
24 Real Parameter
Selection 14
Selection of the input parameter from the Setpoint Parameter Selection List. 0 0…105
25 Real Input Reference
Selection 14
Selects the type of input conditioning for non boolean parameters.
0 = Absolute Value
00
26 Real Test Condition 14 0 = Disabled
1 = Less Than
2 = Greater Than
3 = Equals
0 0…3
27 Real Evaluation Type
14
0 = Magnitude
1 = State
2 = Percent of Reference (not supported in the M5 model)
3 = Percent of Sliding Reference (not supported in the M5 model)
00…3
28 Real Threshold 14 The value, percent, or state that triggers the output action. 0 -10,000,000…
10,000,000
29 Real Hysteresis 14 The value in magnitude or percent of reference at which the output action is deasserted.
Example: A less than condition deasserts at (threshold + hysteresis), a greater than condition
deasserts at (threshold - hysteresis).
0 0…10,000,000
30 Real Assert Delay
Seconds 14
The amount of time to delay the output action after a setpoint trigger occurs. Minimum equals
realtime update rate setting.
0 0.000…3600
31 Real Deassert Delay
Seconds 14
The amount of time to delay deassertion after the setpoint trigger releases. Minimum equals
realtime update rate setting.
0 0.000…3600
Table 66 - Configuration.Setpoints_11_15 Data Table
Element
Number
Type Tag Name Description Default Range