7 Real KYZ_Solid_State_Output_Scale The KYZ output parameter divided by the scale is the output pulse rate.
Example: Wh is selected for the parameter and 1,000 is the scale value. The output is
pulsed every kWh.
1,000 1…
100,000
8 Real KYZ_Pulse_Duration_Setting Set as 50…1000 to indicate the duration of the pulse in milliseconds, or set to 0 for
KYZ-style transition output. (Toggle)
Important: The value for delay is rounded off to the nearest 10 ms internally during
this function.
250 (ms) 0 or 50
…1000
9 Real Output_Relay_1_Output_
Parameter
The parameter selected pulses the relay 1 output at a rate that equals the parameter
value divided by relay 1 scale.
0 = Disable
1 = Wh Fwd
2 = Wh Rev
3 = VARh Fwd
4 = VARh Rev
5 = VAh
6 = Ah
006
10 Real Output_Relay_1_Output_Scale The relay 1 output parameter divided by the relay 1 scale is the output pulse rate.
Example: Wh is selected for the parameter and 1,000 is the scale value. The output is
pulsed every kWh.
1,000 1…
100,000
11 Real Output_Relay_1_Pulse_Duration_
Setting
Set as 50…1000 to indicate the duration of the pulse in milliseconds, or set to 0 for
KYZ-style transition output. (Toggle)
Important: The value for delay is rounded off to the nearest 10 ms internally during
this function.
250 (ms) 0 or 50
…1000
12 Real Output_Relay_2_Output_
Parameter
The parameter selected pulses the relay 2 output at a rate that equals the parameter
value divided by relay 2 scale.
0 = Disable
1 = Wh Fwd
2 = Wh Rev
3 = VARh Fwd
4 = VARh Rev
5 = VAh
6 = Ah
006
13 Real Output_Relay_2_Output_Scale The relay 2 output parameter divided by the relay 2 scale is the output pulse rate.
Example: Wh is selected for the parameter and 1,000 is the scale value. The output is
pulsed every kWh.
1,000 1…
100,000
14 Real Output_Relay_2_Pulse_Duration_
Setting
Set as 50…1000 to indicate the duration of the pulse in milliseconds, or set to 0 for
KYZ-style transition output. (Toggle)
Important: the value for delay is rounded off to the nearest 10 ms internally during
this function.
250 (ms) 0 or 50
…1000
15 Real Output_Relay_3_Output_Paramet
er
The parameter selected pulses the relay 3 output at a rate that equals the parameter
value divided by relay 3 scale.
0 = Disable
1 = Wh Fwd
2 = Wh Rev
3 = VARh Fwd
4 = VARh Rev
5 = VAh
6 = Ah
006
16 Real Output_Relay_3_Output_Scale The relay 3 output parameter divided by the relay 3 scale is the output pulse rate.
Example: Wh is selected for the parameter and 1,000 is the scale value. The output is
pulsed every kWh.
1,000 1…
100,000
17 Real Output_Relay_3_Pulse_Duration_
Setting
Set as 50…1000 to indicate the duration of the pulse in milliseconds, or set to 0 for
KYZ-style transition output. (Toggle)
Important: the value for delay is rounded off to the nearest 10ms internally during
this function.
250 (ms) 0 or 50
…1000