Rockwell Automation Publication 1426-UM001F-EN-P - November 2013 217
Communication Chapter 9
CIP Base Energy Object
The PowerMonitor 5000 unit supports the following attributes and services of
the Base Energy Object, Class Code 0x4E.
Table 34 - Supported Attributes
Energy Object Attribute ID Need in Implementation Access Rule Energy Object Attribute Name PowerMonitor 5000
Implementation
1 Required Get Energy/Resource Type Supported
2 Required Get Energy Object Capabilities Supported
3 Required Get Energy Accuracy Supported
4 Optional Get/Set Energy Accuracy Basis Get only
5 Conditional Get/Set Full Scale Reading Not needed
6 Optional Get Device Status Not supported
7 Optional Get Consumed Energy Odometer Supported
8 Optional Get Generated Energy Odometer Supported
9 Conditional Get Total Energy Odometer Supported
10 Conditional Get Energy Transfer Rate Supported
11 Optional Set Energy Transfer Rate User Setting Not applicable
12 Required Get Energy Type Specific Object Path Supported
13-14 Optional Set Energy Aggregation Paths Not needed
15 Optional Set Energy Identifier Returns Device_Name
16 Optional Set Odometer Reset Enable Not supported
17 Conditional Get Metering State Supported
Table 35 - Supported Services
Energy Service Code Need in Implementation Service Name PowerMonitor 5000
Implementation
Class Instance
01hex Optional Optional Get_Attributes_All Supported
03hex Optional Optional Get_Attribute_List Supported
04hex N/A Optional Set_Attribute_List Not supported
05hex Optional Required Reset Not supported
08hex Optional N/A Create Not supported
09hex N/A Optional Delete Not supported
0Ehex Conditional Required Get_Attribute_Single Supported
10hex N/A Required Set_Attribute_Single Supported
18hex N/A Optional Get_Member Not supported
19hex N/A Optional Set_Member Not supported