Manual

Rockwell Automation Publication 1426-UM001F-EN-P - November 2013 187
Communication Chapter 9
EtherNet/IP Object Model
This section provides the object model for a PowerMonitor 5000 device type on
an EtherNet/IP network. The table below indicates the following:
The object classes present in this device
Whether or not the class is required
The number of instances present in each class
Object Class List
The PowerMonitor 5000 unit supports the following CIP classes.
Table 32 - CIP Object Class List
Object Class Need in Implementation Number of Instances
Identity (1, 1hex) Required 1
Message Router (2, 2hex) Required 1
TCP/IP Interface Object (245, F5hex) Required 1
Ethernet Link Object (246, F6hex) Required 1 Required (2 Optional)
Connection Manager Object (6, 6hex) Required 1
Assembly Object (4, 4 hex) Required Minimum of 3
Parameter Object (15, Fhex) Required Product Specific
Parameter Group Object (16, 10hex) Optional Product Specific
Non-Volatile Storage Object (161, A1hex) Required Product Specific
File Object (55, 37hex) Required Minimum of 1
Time-Sync Object (67, 43hex) Optional 1
QoS Object (72, 48hex) Optional 1
PCCC Object (103, 67hex) Optional 1
Symbol Object (107, 6Bhex) Optional Product Specific
User Defined Template Object (108, 6Chex) Optional Product Specific
File Manager Object (794, 31Ahex) Optional 1
Email Object (815, 32Fhex) Optional 1
Device Level Ring Object (71, 47hex) Optional 1
Energy Object (78, 4Ehex) Required 1
Electrical Energy Object (79, 4Fhex) Required 1