156 Rockwell Automation Publication 1426-UM001F-EN-P - November 2013
Chapter 7 Logic Functions
Log_Status_Input_Changes
These are the choices:
0 = Disable recording of status input changes into the status log
1 = Enable recording of event input changes into the status log
Status_Input_1_Input_Scale
Status_Input_2_Input_Scale
Status_Input_3_Input_Scale
Status_Input_4_Input_Scale
When a status pulse is received the count is increased by the scale factor. (Input
pulse * input scale) added to total status count.
Setup for demand EOI synchronization is described in Basic Metering
on
page 51.
Status
Status input status is reported by the state of the following Boolean tags, found in
the Status.DiscreteIO
table. For each tag, 0 = false, 1 = true.
Status_Input_1_Actuated
Status_Input_2_Actuated
Status_Input_3_Actuated
Status_Input_4_Actuated
The scaled value of status input counters are reported in the following tags, found
in the MeteringResults.Energy_Demand
table.
Status_1_Count_xM
Status_1_Count_x1
Status_2_Count_xM
Status_2_Count_x1
Status_3_Count_xM
Status_3_Count_x1
Status_4_Count_xM
Status_4_Count_x1
These are the semantics:
X 1 = value time 1, range = 0…99,999
X M = value time 1 million, range = 0…9,999,999
Combined range (X M, X 1) = 0…9,999,999,999,999