Chapter 6 Logging
Logging Overview
The PowerMonitor 5000 unit maintains a number of types of internal data logs
and records metering, status, event, and alarm data into these logs as specified in
the logging configuration. This table summarizes the data log types and sizes, and
how their records can be retrieved.
Setup
The following set-up parameters define the behavior of the data logging functions
in the PowerMonitor 5000 unit, except for the Data Log, which has its own set of
set-up parameters. These parameters are found in the Configuration.Logging
table.
Energy_Log_Interval
Energy_Log_Interval selects how often a record is logged, in minutes:
0 = Disables energy logging
1…60 = Length of logging interval in minutes
-1 = Synchronizes energy logging to the end of the demand interval
Energy_Log_Mode
Energy_Log_Mode defines the log behavior when full:
0 = Stop logging
1 = Delete oldest energy log file and create a new file
Log Type Model Max Number of Records Log Data Retrieval Method
Read Selected
Record
Read Records
Sequentially, in
Forward or
Reverse Order
Web File
Download
FTP File
Download
Waveform log M6 21,600 cycles, 256 files
Energy log All 90 days (129,600 @ 1 minute log rate)
Data log All 60,000 @ 32 parameters
Min/Max log All 82 parameters
Load Factor log All 13 Including Current Month
Time-of-Use log All 13 Including Current Month
Alarm log All 100 Alarms
Event log All 100 Events
Setpoint log All 100 Setpoint Events
Power Quality log M6 100
Trigger Data log M6 3,600 cycles, 60 files
Snapshot log M6 2270 parameters 1 file