50 Rockwell Automation Publication 1425-UM001A-EN-P - January 2012
Chapter 3 Software Interface
Read all current and voltage values from the PowerMonitor W250 with Modbus
address 63:
• Modbus address - 0x3F
• Starting register - 0x2B (register 43 decimal)
• Length - 0x06
[3F 03 00 2B 00 06 B1 1E]