Owner manual

Rockwell Automation Publication 1420-UM001D-EN-P - September 2013 57
PowerMonitor 500 Unit Data Tables Appendix A
Table 27 - Configuration - Analog Outputs: Read and Write
Modbus
Address
Length
(words)
Description / Units Data Format Notes
304609 16 Analog output A0: parameters
configuration
CUSTOM Refer to Table 28
304625 16 Analog output A1: parameters
configuration
CUSTOM
Table 28 - Analog Output Configuration Parameters
Modbus
Address
Length
(words)
Description / Units Data Format Notes
Block
address +0
1 Type of the variable that is linked to
the N analog output
UINT
Block
address +1
2 Minimum electric value of the N
analog output
REAL Value min = 0
Value max = 9,999,000
Block
address +3
2 Maximum electric value of the N
analog output
REAL
Block
address +5
2 Minimum output value of the N
analog output
REAL Value min = 0.0
Value max = 100.0
Block
address +7
2 Maximum output value of the N
analog output
REAL
Block
address +9
7 Reserved