Unit Configuration Chapter 3
210 AN OUT 1: User programming of the analog
outputs (0…20 mA).
211 VARIABLES: selects the variable to be
retransmitted by means of the analog output.
212 MIN INPUT: minimum value of the variable
input range, corresponds to the ‘MIN OUTPUT
value of the analog output.
213 MAX INPUT: maximum value of the variable
input range corresponds to the ‘MAX OUTPUT
value of the analog output.
214 MIN OUTPUT: sets the value expressed as %
of the output range (0…20 mA) that corresponds to
the minimum measured value.
215 MAX OUTPUT: selects the value expressed as
% of the output range (0…20 mA) that corresponds
to the maximum measured value.
230 METERS: reset the ENERGY METERS
choosing among:
231 TOTAL, 222 PARTIAL: resets all energy
meters, total and partial.
233 TOTAL +: resets the total meters of imported
energy.
234 TOTAL -: resets the total meters of exported
energy.
235 PARTIAL +: resets the partial meters of
imported energy.
236 PARTIAL -: resets the partial meters of
exported energy.
240 RESET: Resets the MAX or dmd stored values.
250 CLOCK:
251 FORMAT: UE, sets the European time format
as 24h (00:00) or sets the time format as 12h (12:00
AM/PM).
252 YEAR: sets the current year.
253 MONTH: sets the current month.
254 DAY: sets the current day.
255 HOUR: sets the current hour.
256 MINUTE: sets the current minute.
257 SECOND: sets the current second.
260 END:
To save programming changes, press Program/select.
To exit the Programming mode without saving any
changes, press Exit and confirm by pressing
Program/select.
If no buttons are pressed for two minutes, the unit
exits Programming mode without saving changes.
Save the set
parameters and come
back to the measuring
mode.
L ist of available
variables
As AN OUT 1