2. Adjust the ZERO pot until the desired output is achieved.
3. Connect the resistor that represents the span value to the EXC and NEG
terminals.
4. Adjust the SPAN pot until the desired output is achieved.
Repeat these steps until no further adjustment is required.
Specifications
All other trademarks are the property of their respective holders, and are hereby acknowledged.
TIP
If the unit uses a three-wire sensor, a jumper must be placed
between EXC and SEN.
Strap-on Temperature Sensor Specifications
Specification Value
Standard Length 2”
Operating Temperature Range -20 … 105 ºC (-4 … 221 ºF)
Ambient Temperature Range 0 … 70°C (32 … 158°F)
Cable Type PVC insulated, parallel bonded
Wiring Connections Terminal blocks
Enclosures ABS or Weatherproof
Sensor Types 1 k Platnium RTD