6 Electronic to Pneumatic Transducer
Publication 1414-IN006A-EN-P - October 2005
Specifications
Electronic to Pneumatic Transducer Specifications
Specification Value
Input Signal 4…20mA, 0…10V dc jumper selectable
Input Impedance 4…20mA input, 400 Ω minimum, 550 Ω maximum
Power Supply 4…20mA input, Loop powered; 1.0 Watt maximum
Air Supply 138 kPa (20 psig) nominal, 207 kPa (30 psig) maximum Clean, dry, oil-free
air required.
Air Consumption 5.66 ml/s (0.012 scfm) @ 138 kPa (20 psig) supply, maximum
Output Air Capacity 141 ml/s (515 scim) maximum @ 138 kPa (20 psig) supply
Air Connections Male barbed fittings for flexible 1/4” OD pneumatic tubing
Wiring Connections Screw terminals for 14 … 22 AWG wire
Output Signal 21…103 kPa (3-15 psig) nominal, direct acting
Manufacturing Process ISO 9002 certified
Linearity ±1% of span
Hysteresis ±1% of span
Adjustments Zero and span potentiometers
Operating Temperature 0°C … 60°C (32°F … 140°F)
Operating Humidity 5…95% RH, non-condensing
Dimensions H x W x D (Snap-Track
model)
83mm x 70mm x 50mm (3.25” x 2.75” x 2”)
Dimensions H x W x D ABS model) 116mm x 84mm x 53mm (4.55” x 3.3” x 2.1”)