5. Jumper the amperage range selected from sensor label chart.
Remove the jumper for the None position. This example illustrates a 20 A mode.
Specifications
Technical Specifications - Current Sensor
Attribute 1414-CCZ10FZWZDC, 1414-CCZ10FZWZDD, 1414-CCZ10FZWZDE,
1414-CCZ10FZWZDA
Power supply Self-powered
Response time 100 ms (0…90%)
AC conductor hole Split core - 24 mm x 19 mm (0.95 in. x 0.75 in.)
Solid core - Ø20 mm (0.8 in.)
Output loading error (0…10V) Calibrated with 1 MΩ load, add 1.2% error with 100 KΩ
Enclosure size Split Core - 70 mm x 87 mm x 30 mm
(2.75 in. x 3.45 in. x 1.2 in.)
Solid Core - 49 mm x 87 mm x 25 mm
(1.95 in. x 3.45 in. x 1.0 in.)
Operating temperature range 0…40 °C (32…104 °F)
Protection circuitry Revers voltage protected and output limited
Wiring connections Split Core - Screw terminal block (14 …22 AWG)
Solid Core - Barrier strip
Enclosure material UL 94 V-0 flammability rated ABS, insulation class 600V
Output signal accuracy 0…5V DC and 0…10V DC (Better than ±1% FS on all three ranges)
Frequency 40…100 Hz
Certifications cULus, RoHS compliant, CE certified
Current Senors Amp Ranges
Model Output Amp Range Max Amp
1414-CCZ10FZWZDC 0…10V DC 0…10 140
1414-CCZ10FZWZDD 0…10V DC 0…25 160
1414-CCZ10FZWZDE 0…10V DC 0…50 190
1414-CCZ10FZWZDA 0…10V DC 0…10, 0…20, 0…50 80, 120, 200
Amperes Jumper
0…50 HIGH
0…20 MID
0…10 NONE
HIGH
MID
Input