Manual
Publication 1413-UM001C-EN-P - May 2006
28 Installation
N7:10 Capacitor
Step 1 -
Effective
Size
kVAR Nameplate capacitor size for each step 50 10 Configuration
N7:11 Capacitor
Step 2 -
Effective
Size
kVAR 50 11 Configuration
N7:12 Capacitor
Step 3 -
Effective
Size
kVAR 50 12 Configuration
N7:13 Capacitor
Step 4 -
Effective
Size
kVAR 50 13 Configuration
N7:14 Capacitor
Step 5 -
Effective
Size
kVAR 50 14 Configuration
N7:15 Capacitor
Step 6 -
Effective
Size
kVAR 50 15 Configuration
N7:16 Capacitor
Step 7 -
Effective
Size
kVAR 50 16 Configuration
N7:17 Capacitor
Step 8 -
Effective
Size
kVAR 50 17 Configuration
N7:18 Capacitor
Step 9 -
Effective
Size
kVAR 50 18 Configuration
N7:19 Capacitor
Step 10 -
Effective
Size
kVAR 50 19 Configuration
N7:30 Capacitor
Discharge
Time
seco
nds
The amount of time after a capacitor step is
turned off, before a capacitor step is considered
fully discharged
60 30 Configuration
N7:31 Nominal
Voltage
volts The nominal bus voltage of the system 480 31 Ext
Configuration
1
Control and Status Parameters
Address Parameter Unit Description Range Default DAT
INT
PanelView
Screen