Owner's manual

Rockwell Automation Publication 1413-UM001D-EN-P - November 2010 61
Operation Chapter 4
Navigation/Menu Screen
Bank Status Screen
The status for the steps is listed in vertical columns from 1…10. There are no
configurations on this screen. It displays status data only.
Mode: A = Automatic, which means the step is controlled based on the operation
mode selected. M = Manual, which means you can force the step on or off via the
keypad.
Step Status: 1 = On, 0 = Off.
Discharge Status: ‘ ’ = Not Discharging, D = Discharging.
Alarm: ‘ ’ = No Alarm, ‘A’ = In Alarm.
You can press Extended Status to navigate to the Extended Status Screen.
Press Menu then Overview to return to the Overview Summary Screen.