installation and operation Manual

Page
8
5.6 Ground FaultTime Settings
The ground fault time delay is a flat response with four
settings
(I,
.15, .3,
.5
second) available (Figure 12-3).The
I
setting gives a trip response with no intentional delay
(Instantaneous). This option is available on Catalog Nos.
LSG and LSIG.
6.OTESTING
6.1 Functional Field Testing
A test receptacle is built into each trip unit to allow use of
the STK2 Test Kit. The Test Kit performs a test of the Long
Delay, Short Delay and Ground Fault functions.
6.2
6.2.1 Code Requirements
The National Electrical Code under Article 230
-
95
-
C
requires that any ground
-
fault protection system be
performance tested when first installed. The test shall be
conducted in accordance with approved instructions
I
\
I
I\
Remove-
I
LTest
Jacks
Fig.
11
Adjustment Switches and Test Points
5
3@7
Short
Delay Pickup
(Multiples
of
Rated
Current
1,)
Current
W
+
E
I
Ih
1
Ilh
5
Short Delay Pick
-
up
(Multiples
of
Rated
Cu
Current
irrent)
Fig.
12-1
Short Delay Trip Current Adjustment and Curve
Details
Fig.
12-2
Short Delay Trip Current and Short Delay Trip
Time Adjustment and Curve Details
40752-072(2) Effective
6/02
Performance Testing for Ground Fault Trip Units