9. Measures to be taken if operating faults occur
The circuit-breaker fails to open when the opening pushbutton is pressed
Faults
The circuit-breaker fails to open because opening coil has tripped
The circuit-breaker fails to open because undervoltage release undervoltage has tripped
The circuit-breaker fails to open when the protection relay release test is performed
The circuit-breaker fails to close when the closing pushbutton is pressed
The circuit-breaker fails to close because closing coil has tripped
The closing springs cannot be loaded with the manual loading lever
The closing springs cannot be loaded with the spring-loading motor
The circuit-breaker cannot be locked in the open position
Possible causes
Checks and solutions
The opening solenoid of the relay is not
connected properly
Make sure that the opening solenoid is con-
nected correctly
Relay tripping signal not reset
Press the mechanical pushbutton to reset the
relay tripping signal
Supply votage of the auxiliary circuits too
low
Measure the voltage: it must not be less than
85% of the rated voltage of the coil
Supply voltage different from the value indi-
cated on the nameplate of these releases
Check the voltage indicated on the nameplate of
the releases
Faulty switching circuit
Check the connections, fuses, interlocks, protec-
tion switches and accept contacts
Loose clamping screws of the wires and
auxiliary circuits
Make sure that the wire clamping screws are
tight
Incorrect electrical connections in the
power supply circuit
Check the connections with the relative func-
tional diagram
Coil damaged Replace the coil
Operating mechanism locked
Operate in the manual mode. Contact AB if the
fault persists
Open position key lock activated Unlock by inserting the key
Undervoltage release not energized
Check the relative supply circuit and the supply
voltage
Shunt opening release remains perma-
nently energized
Check the supply circuit
Operating mechanism locked Call Rocwell Automation
The fuse that protects the spring loading
motor protection has tripped
Replace the fuse
Faulty gearmotor for automatic spring
loading
Replace the gearmotor
Circuit-breaker closed
Press the opening pushbutton and activate the
lock
Lock in open position defective Call AB
WARNING: If the fault or failure of the circuit-breaker in your application could cause injuries, material damage
or is highly critical, the circuit-breaker itself must be immediately removed so that it can be inspected or repaired.