User Manual

DIR 1000587R0002 (L3821)
(30)
3.5.2 Table of error and warning messages
Allmessageswhichcanbeshownonthedisplay,relatingtoincorrectcongurations,genericalarmsorderivingfromprotectionfunctions,and
linkedtousefulinformation,aredescribedbelow.
Thefollowingsymbolsinthewarningsignalshavethefollowingmeanings:
= Warningsignal/Protectioninalarmmode,withnotrip(trip=off)
= Protectioninalarmmode,withtriponendoftiming(trip=on)
= Information,noaction,exceptingdisplaybyrelay
Alarm message Description Notes
Harmonicdist. Harmonicdistortionalarm Busbarcurrentswithzonefactor>2.1
Contactwear Contactwearalarm Contactwear=100%
G(TRIPOFF) AlarmforprotectionG
TAlarm AlarmforprotectionT Temperatureoff-range
 T(TRIPOFF) AlarmforprotectionT
Ualarm ProtectionUalarm ProtectionUundertiming
LC1Load  AlarmforloadcontrolLC1
LC2Load  AlarmforloadcontrolLC2
L1Sensor  AlarmforL1phasecurrentsensor PhaseL1sensordisconnectedorfaulty
 L2Sensor  AlarmforL2phasecurrentsensor PhaseL2sensordisconnectedorfaulty
L3Sensor  AlarmforL3phasecurrentsensor PhaseL3sensordisconnectedorfaulty
 NeSensor AlarmforNephasecurrentsensor PhaseNesensordisconnectedorfaulty
 TCdisconnected TripCoildisconnectedorfaulty
RatingPlug RatingPlugErrorabsentorfaulty
Phasecycle Phasecycleinverted
Invaliddate Clockinformationlost
CBstatus CBstatuserror ProbableerrorinQ26and/orQ27
Installation Keyplugerror
CBnotdened
Stateofcircuitbreakerinconsistent(Open/Closed)
ProbableerrorinQ26and/orQ27
LocalBus LocalBuserror
Contactwear Contactwearprealarm Contactwear80%
Lprealarm ProtectionLprealarm
Tprealarm ProtectionTprealarm
WarningIw Iwthresholdexceeded
TimingL TimingprotectionL
TimingS TimingprotectionS
TimingG TimingprotectionG
TimingU TimingprotectionU
3.5.3 Error messages displayed in pop-up window
Allmessagesthatappearonthedisplayinapop-upwindowaredescribedbelow.
Error message Description
Wrongpassword
Sessionimpossible Aprogrammingsessioncannotbeopenedduetoacontingentsituation(e.g.timinginprogress)
 Valueoff-range Valuebeyondtheestablishedlimits
Failed1001/2001 InconsistentthresholdsofprotectionsLandS1
Failed1002/2002 InconsistentthresholdsofprotectionsIandS
Failed3001 Inconsistencyastolanguagechange
Failed3003 InconsistencyastoexternalNeutralconguration
Exception6 Controltemporarilyunavailable
Unavailable Functionisnotavailable
Invaliddate  Datehasnotbeenset
Parametersrevised Programmingsessionconcludedcorrectly
Cancelled Programmingsessioncancelled
Failed Programmingsessionrejected