User Manual
DIR 1000587R0002 (L3821)
(19)
3.2.6.2 Uninstalling
TocompletetheuninstallprocedureofaLSIG-MMunit,followthestepsbelow:
1. Withthecircuitbreakeropenand/orisolated,powertheunitfromthebatteryunit
2. Entertheunit’s“Settings”menu
3. Select“Circuit breaker”
4. Select“Unit installation”
5. Inputthepassword
6. Select“Uninstall”andpress“ENTER”
7. Removethebatteryunit
8. RemovetheLSIG-MMunitfromthecircuitbreaker
Itisnotstrictlynecessarytocomplete
theuninstallingprocedure,butthisenablestheparametersrelatingtothecircuitbreaker,suchascontact
wearandothers,tobesaved,otherwisethesedatawouldbelost.ThedatainquestionarethentransmittedtothenewLSIG-MMunitinstalled
onthesamecircuitbreaker.
3.3 Userinterface
Description of icons displayed
Description Symbol
Remotecontrol
Fixedicon:dataloggerenabled
Flashingicon:triggeringaccomplished
Vauxinstalled
Parameterchange
Ref. Description
1 SerialnumberoftheCB
2 AlarmindicatorLED
3 Pre-alarmindicatorLED
4 TESTconnectorforconnectingortestingthereleasebymeansofbatteryunit
5 Graphicdisplay
6 ENTERkeyforconrmingdataorchangingpage
7 Buttonforthecursor(UP)
8 Buttonforthecursor(DOWN)
9 Testand“iTest”infobutton
10 Pushbuttonforexitingthesub-menusorforcanceling(ESC)
11 Ratingplug
910
1
2
3 4 5
6 7
8
11
TheGraphicDisplayisLCDtypewith128x64pixelsandwhenthereisanauxiliaryvoltage,thebacklitandtheammeterarealwaysactive.
Thedisplayisalsoactiveinself-poweringmodewithaminimumbusbarcurrent.
Contrastonthedisplaycanbeadjustedbymeansofthespecicfunctionavailableontheuserinterfacesettingsmenu(par.3.4.4.1).