User Manual

DIR 1000587R0002 (L3821)
(17)
L
(t=k/I
2
)   0.4xIn
I
1
1xIn 3st
1
144s
(1)
,step3s
Releasebetween
±10%,I
f
6In
curvesIEC60255-3
step0.01xIn t1@3I
1
1.05and1.2xI1±20%,I
f
>6In
S
1
    0.6xIn I
2
10xIn Min,0.05st
2
0.8s,step0.01s ±7%,I
g
6In Thebestofthetwodata
(t=k) step0.1xIn 0.10st
2start-up
30s,step0.01s ±10%,I
g
>6In ±10%or40ms
0.6xIn I
2start-up
10xIn 0.04st
2sel
0.20s,step0.01s
step0.1xIn
S
1
   0.6xIn
I
2
10xIn 0.05st
2
0.8s, ±7%,I
g
6In ±15%,I
g
6In
(t=k/I
2
) step0.1xIn step0.01at10xIn ±10%,I
g
>6In ±20%,I
g
>6In
I     1.5xIn I
3
15xIn 30ms ±10%
(t=k) step0.1xIn
G
(3)
    0.20xIn I
4
1xIn
0.1st
4
1s,step0.05s Thebestofthetwodata
(t=k) step0.02xIn 0.1st
4start-up
1s,step0.02s ±7% ±10%or40ms
0.04st
4sel
0.2s,step0.01s
whenI>I4
G
(3)
    0.20xIn I
4
1xIn
0.1st
4
1s,step0.05s ±7% ±15%
(t=k/I
2
)
step0.02xIn @I
g
>4In
U     2% I
6
90% 0.5st
6
60s,step0.5s ±10%Thebestofthetwodata
(t=k) step1%  ±10%or40ms
OT     Fixed,dened Instantaneous ±5°C _____
(temp=k) byAB
Iinst     Automatic,dened Instantaneous
byAB
MM     1.5xIn I
5
4xIn 30ms ±10%
(t=k) step0.1xIn
Load control    50%÷100%step0.05xI
1
LC1/LC2
Warning Iw     0,3÷10I
n
step0,05xI
n
±10% 10÷40ms
3.1.9.9 Summary table of the protection function settings for the LSIG-MM
Protection
Threshold
range
Time Tolerance
(2)
Time
range
Threshold
tolerance
(2)
Disabling
Disabling
TRIP only
Start-up threshold
Thermal memory
(1)
Theminimumvalueofthistripis1sregardlessofthetypeofcurveset(self-
protection)
(2)
Thesetolerancesapplyunderthefollowingconditions:
- self-powered relay at full power (without start-up)
- presence of auxiliary power supply
- two-phase or three-phase power supply
-presettriptime100ms
(3)
ProtectionGisdisabledforcurrentvaluesgreaterthan4In,whereI4<0.4
In,greaterthan6In,where0.5InI4<0.8Inandgreaterthan8InwhereI4
0.8In.
Forallcases notcovered by the above assumptions, the following tolerance
valuesapply
Protections Trip threshold Trip time
L Releasebetween1.05and1.25xI1 ±20%
S ±10% ±20%
I ±15% 60ms
G ±10% ±20%
Others ±20%
3.1.9.10 Table of measurements
Typeofmeasurement Tolerance
Range %
Phaseandneutralcurrents 0.3...6In 1.5
Internalgroundfaultcurrent 0.3...4In 1.5
(internalsourcegroundreturn)
Peakfactor 0.3...6In 1.5