User Manual
92 Publication 1408-UM001B-EN-P - May 2008
Appendix A Powermonitor 1000 Data Tables
User Configurable Table Setup Parameters
CSP File No. N36
CIP Instance 29
Applies to EM3 only
No. of Elements 17
No. of Words 17
Data Type Integer
Data Access Read/Write
User Configured Table Setup
Element
No.
Modbus
Address
Element Name Default Value Range Description
0 41001 Password 0 0…9999 Required for configuration,
returns -1.
1 41002 Selection for Parameter #1 29 (L1 Current) 0…110
2 41003 Selection for Parameter #2 30 (L2 Current)
3 41004 Selection for Parameter #3 31 (L3 Current)
4 41005 Selection for Parameter #4 37 (L1-L2 Voltage)
5 41006 Selection for Parameter #5 38 (L2-L3 Voltage)
6 41007 Selection for Parameter #6 39 (L3-L1 Voltage)
7 41008 Selection for Parameter #7 41 (Frequency)
8 41009 Selection for Parameter #8 52 (Total Real Power)
9 41010 Selection for Parameter #9 56 (Total Reactive Power)
10 41011 Selection for Parameter #10 60 (Total Apparent Power)
11 41012 Selection for Parameter #11 48 (3 Phase True Power Factor)
12 41013 Selection for Parameter #12 70 (Real Energy Net (kWh))
13 41014 Selection for Parameter #13 62 (Status 1 Count x1)
14 41015 Selection for Parameter #14 64 (Status 2 Count x1)
15 41016 Selection for Parameter #15 79 (Real Power Demand)
16 41017 Selection for Parameter #16 8 (Status Input States)