User Manual

16 Publication 1408-UM001B-EN-P - May 2008
Chapter 3 Communications Command Summary
Modbus RTU Serial and
Optional Modbus/TCP
Ethernet
The power monitor does not initiate Modbus commands but responds
to commands sent by the Modbus master. These Modbus function
codes are supported.
03 Read Holding Registers
04 Read Input Registers
16 Write Multiple Holding Registers
08 Diagnostics
00 Echo Command Data
02 Return Diagnostic Counters
10 Clear Diagnostic Counters
06 Write Single Holding Register