User Manual, PRIOR to Firmware rev. 3.0 Owner manual

Publication 1404-UM001D-EN-E - October 2004
Communications 4-37
The Powermonitor 3000 supports the following network requests:
IMPORTANT
Please give particular attention to the messaging and
software version compatibility information in the
table. If you are replacing a Series A Ethernet
Powermonitor 3000 with a Series B unit, you may
need to upgrade software or modify the
communications programming of your controller
ladder programming or client application to
re-establish communications.
Table 4.10 Series A and Series B Comparison
Function Series A (Comms FRN
2.01 or 2.02)
Series B
Communications protocol CSP (PCCC) and/or
EtherNet/IP
EtherNet/IP only
Encapsulated PCCC
(Comms FRN 1.22 or later)
Protocol select Yes N/A
Bootp support Yes No
Data rate 10 Mbps 10/100 Mbps
Web page Fixed web page Configurable web page
Flash upgradeable Uses special loader Uses ControlFlash
LED indicators Link, RX, TX LNK, ACT, STATUS`
Network Demand Synch No Yes
SNTP capable No Yes
I/O Communications No Yes
CIP Generic messaging Yes Yes
PLC-5 Typed CIP messaging Yes Yes
CIP Data Table messaging Yes Yes, Comms FRN 1.21 or
later
SLC 500 Typed CIP messaging Yes Yes, Comms FRN 1.21 or
later
RSPower32 support 2.10 and later 2.40 and later
RSEnergyMetrix support Yes Yes
RSEnergy support 2.00.13 (CSP only) No, upgrade to
RSEnergyMetrix