User Manual, PRIOR to Firmware rev. 3.0 Owner manual

Publication 1404-UM001D-EN-E - October 2004
Powermonitor 3000 EtherNet/IP Device Profile F-11
Supported PCCC Commands
The PCCC object supports the following PCCC commands:
PLC-5 Typed Write
PLC-5 Typed Read
Protected Typed Logical Read, 2 address fields
Protected Typed Logical Write, 2 address fields
Word Range Read
Word Range Write
These commands are supported on the Logix 5, SLC 500 and
ControlLogix processors and are used by network devices to send
data to, or receive data from the PM 3000. Both commands provide
implicit data type information within their address fields which is used
by the DC to validate the read before the data items are sent.
The last four items in the list above are supported only in Series B
Powermonitor 3000 units with communications firmware 1.22 or later.
Section 5.3.5.81 of Programmable Controller Communication
Commands provides the full details regarding these commands.
NVS Object
The Non-Volatile Storage (NVS) Object provides access to the DC’s
non-volatile flash memory. It provides a mechanism for writing to the
defined instances of that object. Because the NVS Object is a vendor
specific object, it is not defined in the CIP Common Specification.
Class Attributes
Table F.21
Class Code: A1 hex
Table F.22
Attr ID Access Name Data Type Default
Value
1 Get Revision UINT 1
2 Get Max Instance UINT 2