User Manual, PRIOR to Firmware rev. 3.0 Owner manual
Publication 1404-UM001D-EN-E - October 2004
Technical Specifications D-5
Table D.5 General Specifications
Dielectric Withstand Control Power 2000 Volts
Voltage Inputs 2000 Volts
Current Inputs 2000 Volts
Status Inputs 500 Volts
Control Relays 1600 Volts
Terminal Blocks Power Supply and Voltage input
Terminals
12 AWG (4 mm2) max.,
9 lb-in (1.02 Nm) Torque.,
75°C or Higher Copper Wire only
Relay, KYZ outputs, Current input
terminals
(1)
14 AWG (2.5 mm2) max., 10.4 lb-in (1.18 Nm) Torque.,
75°C or Higher Copper Wire only
Status inputs, RS485 14 AWG (2.5 mm2) max.,
5 lb-in (0.56 Nm) Torque
RIO, DNT (When present) 14 AWG (2.5 mm2) max.,
5 lb-in (0.56 Nm) Torque
Operating Temperature -20°C to +60°C (-40°F to +140°F) Cat. No. 1404-DM, 1404-Mxxxx-000, 1404-Mxxxx-DNT
+0°C to +55°C (+32°F to +131°F) 1404-Mxxxx-232, -RIO, -ENT, -CNT
Storage Temperature -40°C to +85°C (-40°F to +185°F)
Humidity 5% to 95%, Noncondensing
Vibration 10 to 500 Hz: 2G Operational (±0.012 in.)
Shock 1/2 Sine Pulse, 11 ms duration: 30G Operational and 30G Nonoperational
(1)
Recommended Ring lug: AMP part # 320634