User Manual, PRIOR to Firmware rev. 3.0 Owner manual

Publication 1404-UM001D-EN-E - October 2004
D-4 Technical Specifications
General Input, Output, and Environmental Ratings
Table D.2 Input and Output Ratings
Control Power 1404-xxxxA-xxx 102V-264V ac 47-63 Hz or
106V-275V dc
(0.2 Amp maximum loading)
1404-xxxxB-xxx 18V to 50V dc (15 VA maximum loading)
Voltage Sense
Inputs: V1, V2, V3
Input Impedance: 1M ohm minimum, 399V ac maximum; V1, V2 and
V3 to N.
Current Sense
Inputs: I1, I2, I3, I4
Overload Withstand:
15 Amps Continuous,
200 Amps for one second
Burden: 0.05 VA
Impedance: 0.002 ohms
Maximum Crest Factor at 5A is 3
Starting Current: 5 mA
Status Inputs Contact Closure (Internal 24Vdc)
Control Relay
KYZ Output
(1) ANSI C37.90-1989 trip duty
(1) Solid State KYZ - 80mA at 240Vdc-300Vdc
Table D.3 Control Relay
(1)
(1)
Meets ANSI/IEEE C37.90-1989 standards for trip duty.
Rating 50/60 Hz AC rms DC
Maximum Resistive Load
Switching
10A at 250V
(2500VA)
10A at 30V and 0.25A at
250V
Minimum Load Switching 10mA at 24V 10mA at 24V
UL 508, CSA 22.2, IEC Rating
Class
B300 Q300
Maximum Make Values
(Inductive Load)
30A at 120V
15A at 240V
(3600VA)
0.55A at 125V
0.27A at 250V
(69VA)
Maximum Break Values
(Inductive Load)
3A at 120V
1.5A at 240V
(360VA)
0.55A at 125V
0.27A at 250V
(69VA)
Maximum Motor Load
Switching
1/3 HP at 125V
1/2 HP at 250V
Table D.4 Relay Life
(1)
(1)
Meets ANSI/IEEE C37.90-1989 standards for trip duty.
Parameter Number of Operations
Mechanical
5 X 10
6
Electrical
1 X 10
5