User Manual, PRIOR to Firmware rev. 3.0 Owner manual
Publication 1404-UM001D-EN-E - October 2004
C-30 Sample Applications
The message configuration for the ReadOld message is shown below.
The message configuration for writing the new configuration table to
the Powermonitor 3000 is shown below.
Start
This rung inserts a brief time delay before enabling the WriteNew message instruction.
msgReadOld.DN
TON
Timer On Delay
Timer Timer1
Preset 100
Accum 0
EN
DN
Timer On Delay
Timer Timer2
Preset 4000
Accum 0
EN
DN
After clearing the flags from the previous write, this rung performs a data table write to transfer the selected user
configured data table setup to the Powermonitor 3000. If the number of paramaters in the User Configurable Data
Table is changed, the Powermonitor 3000 resets.
1
2
Timer1.DN
ONS
Oneshot_2 Success
U
Failed
U
MSG
Type - PLC-5 Typed Write
Message Control msgWriteNew
EN
DN
ER
msgWriteNew.DN
Counter1.CU
TON