User Manual, PRIOR to Firmware rev. 3.0 Owner manual

Publication 1404-UM001D-EN-E - October 2004
Powermonitor 3000 Data Tables A-69
Element
No.
Modbus
Address
Element name Range Units Comment
0 32501-02 Off-peak apparent
energy
-999,999.0 to
999,999.0
MVAh Refer to Reading Time-of-Use Log Data on
page 7-18
1 32503-04 Off-peak apparent
energy
-999.999.999 to
999.999.999
kVAh
2 32505-06 Off-peak demand VA
0.0 to 999.9 x 10
21
VA
3 32507-08 Mid-peak apparent
energy
-999,999.0 to
999,999.0
MVAh
4 32509-10 Mid-peak apparent
energy
-999.999.999 to
999.999.999
kVAh
5 32511-12 Mid-peak demand VA
0.0 to 999.9 x 10
21
VA
6 32513-14 Peak apparent energy -999,999.0 to
999,999.0
MVAh
7 32515-16 Peak apparent energy -999.999.999 to
999.999.999
kVAh
8 32517-18 Peak demand VA
0.0 to 999.9 x 10
21
VA
9 32519-20 Start date 000101 to 991231 YYMMDD Start month / day for data stored in this
record, inclusive
10 32521-22 End date 000101 to 991231 YYMMDD End month / day for data stored in this
record, inclusive
11 33523-24 Record number 0 to 12
Table A.59 Parameters for Trend Log and Configurable Table
Applies to: Table A.21 Trend Log Configuration/Read-Back Record Select
Table A.22 Trend Log Results
Table A.30 User-Configured Table Setup
Table A.31 User-Configured Table Results
PM3000 Type All
Param
No.
Parameter name Comment
0 None No parameter
1 Relay output status Refer to Table A.3 Discrete Data
2 Solid-state KYZ output status
3 Alarm output word
4 Status inputs state
5 Status input #1 counter
6 Status input #2 counter
7 Voltage Mode (Wiring Configuration) Refer to Table A.4 Basic Device Configuration
8 PT Primary
9 PT Secondary
10 I1/I2/I3 CT Primary
11 I1/I2/I3 CT Secondary
12 I4 CT Primary
13 I4 CT Secondary