User Manual, PRIOR to Firmware rev. 3.0 Owner manual
Publication 1404-UM001D-EN-E - October 2004
A-68 Powermonitor 3000 Data Tables
Element
No.
Modbus
Address
Element name Range Units Comment
0 32401-02 Off-peak reactive
energy
-999,999.0 to
999,999.0
MVARh Refer to Reading Time-of-Use Log Data on
page 7-18
1 32403-04 Off-peak reactive
energy
-999.999.999 to
999.999.999
kVARh
2 32405-06 Off-peak demand
VARs
0.0 to 999.9 x 10
21
VAR
3 32407-08 Mid-peak reactive
energy
-999,999.0 to
999,999.0
MVARh
4 32409-10 Mid-peak reactive
energy
-999.999.999 to
999.999.999
kVARh
5 32411-12 Mid-peak demand
VARs
0.0 to 999.9 x 10
21
VAR
6 32413-14 Peak reactive energy -999,999.0 to
999,999.0
MVARh
7 32415-16 Peak reactive energy -999.999.999 to
999.999.999
kVARh
8 32417-18 Peak demand VARs
0.0 to 999.9 x 10
21
VAR
9 32419-20 Start date 000101 to 991231 YYMMDD Start month / day for data stored in this
record, inclusive
10 32421-22 End date 000101 to 991231 YYMMDD End month / day for data stored in this
record, inclusive
11 33423-24 Record number 0 to 12
Table A.58 Time of Use Records – Apparent Energy and Demand
CSP File No. F58
Remote I/O BT 53
CIP Assy. Inst. 74
No. of Elements 12
User Configurable No
Data Type Floating point
Data Access Read only
PM3000 Type All