User Manual, PRIOR to Firmware rev. 3.0 Owner manual

Publication 1404-UM001D-EN-E - October 2004
Powermonitor 3000 Data Tables A-67
Element
No.
Modbus
Address
Element name Range Units Comment
0 32301-02 Off-peak real energy -999,999.0 to
999,999.0
MWh Refer to Reading Time-of-Use Log Data on
page 7-18
1 32303-04 Off-peak real energy -999.999.999 to
999.999.999
kWh
2 32305-06 Off-peak demand
0.0 to 999.9 x 10
21
Watts
3 32307-08 Mid-peak real energy -999,999.0 to
999,999.0
MWh
4 32309-10 Mid-peak real energy -999.999.999 to
999.999.999
kWh
5 32311-12 Mid-peak demand
0.0 to 999.9 x 10
21
Watts
6 32313-14 Peak real energy -999,999.0 to
999,999.0
MWh
7 32315-16 Peak real energy -999.999.999 to
999.999.999
kWh
8 32317-18 Peak demand
0.0 to 999.9 x 10
21
Watts
9 32319-20 Start date 000101 to 991231 YYMMDD Start month / day for data stored in this
record, inclusive
10 32321-22 End date 000101 to 991231 YYMMDD End month / day for data stored in this
record, inclusive
11 33323-24 Record number 0 to 12
Table A.57 Time of Use Records – Reactive Energy and Demand
CSP File No. F57
Remote I/O BT 52
CIP Assy. Inst. 73
No. of Elements 12
User Configurable No
Data Type Floating point
Data Access Read only
PM3000 Type All