User Manual, PRIOR to Firmware rev. 3.0 Owner manual

Publication 1404-UM001D-EN-E - October 2004
A-66 Powermonitor 3000 Data Tables
Table A.55 Time of Use Register Configuration
CSP File No. N55
Remote I/O BT 49
CIP Assy. Inst. 70 (Write), 71 (Read)
No. of Elements 10
User Configurable No
Data Type Integer
Data Access Read / Write
PM3000 Type All
Element
No.
Modbus
Address
Element name Range Default Comment
0 42201 Password -1 to 9999 0 Required for configuration, -1 for readback select,
Returns -1
1 42202 Record to read back 0 to 12 0 Refer to Configuring the Time-of-Use Log on page 7-17
2 42203 Reserved 0 0
3 42204 Write command 0 to 1 0
4 42205 Log day 1 to 31 31
5 42206 Off peak day 0 to 127 65
6 42207 Mid peak a.m. 0 to 4095 1792
7 42208 Mid peak p.m. 120
8 42209 Peak a.m. 2048
9 42210 Peak p.m. 7
Table A.56 Time of Use Records – Real Energy and Demand
CSP File No. F56
Remote I/O BT 51
CIP Assy. Inst. 72
No. of Elements 12
User Configurable No
Data Type Floating point
Data Access Read only
PM3000 Type All