User Manual, PRIOR to Firmware rev. 3.0 Owner manual

Publication 1404-UM001D-EN-E - October 2004
Powermonitor 3000 Data Tables A-65
Table A.53 Controller Command
CSP File No. N53
Remote I/O BT -
CIP Assy. Inst. 67
No. of Elements 1
User Configurable No
Data Type Integer
Data Access Write only
PM3000 Type Series B Ethernet only
Element
No.
Element name Range Default
Value
Comment
0 Controller Command
Bits 0
0 to 32767 0 Refer to Network Demand / Time
Configuration on page 3-29
Table A.54 Daylight Saving Time Configuration
CSP File No. N54
Remote I/O BT 47
CIP Assy. Inst. 68 (Write), 69 (Read)
No. of Elements 10
User Configurable No
Data Type Integer
Data Access Read / Write
PM3000 Type All
Element
No.
Modbus
Address
Element name Range Default Comment
0 42101 Password -1 to 9999 0 Required for configuration. Returns -1
1 42102 DST Enable 0 to 1 0 0 = Disabled, 1 = Enabled
2 42103 DST Start Month 1 to 12 4 1 = January, 2 = February, etc.
3 42104 DST Start Day 0 to 6 0 0 = Sunday, 1 = Monday, etc.
4 42105 DST Start Day Instance 1 to 5 1 1 = 1st, 2 = 2nd, ... 5 = Last
5 42106 DST Start Hour 0 to 23 2 0 = 12:00 midnight, 1 = 1:00 AM, etc.
6 42107 DST End Month 1 to 12 10 1 = January, 2 = February, etc.
7 42108 DST End Day 0 to 6 0 0 = Sunday, 1 = Monday, etc.
8 42109 DST End Day Instance 1 to 5 5 1 = 1st, 2 = 2nd, ... 5 = Last
9 43110 DST End Hour 0 to 23 2 0 = 12:00 midnight, 1 = 1:00 AM, etc.