User Manual, PRIOR to Firmware rev. 3.0 Owner manual
Publication 1404-UM001D-EN-E - October 2004
A-64 Powermonitor 3000 Data Tables
Table A.52 Network Demand Sync and Time Configuration
CSP File No. N52
Remote I/O BT -
CIP Assy. Inst. 65, 66
No. of Elements 20
User Configurable No
Data Type Integer
Data Access Read / Write
PM3000 Type Ethernet Series B
Element
No.
Modbus
Address
Parameter name Range Default
Value
Description
0 41901 Password 0 to
9999
0 On a write, the correct password is required to change
configuration data. On a read, -1 is returned.
1 41902 Input mode 0 to 3 3 Refer to Network Demand / Time Configuration on
page 3-29.
2 41903 Broadcast port number 300 to
400
300
3 41904 Time server IP address-byte
1
0 to 255 0
4 41905 Time server IP address-byte
2
5 41906 Time server IP address-byte
3
6 41907 Time server IP address-byte
4
7 41908 Time zone -12 to 12 0
8 41909 Time set update interval 0 to
32766
60 (Sec)
9 41910 SNTP IP address 2, octet 1 0 to 255 0 SNTP IP address 2 is a back-up server address when
the first address fails.
10 41911 SNTP IP address 2, octet 2 0
11 41912 SNTP IP address 2, octet 3 0
12 41913 SNTP IP address 2, octet 4 0
13 41914 SNTP IP address 3, octet 1 0 SNTP IP address 3 is a back-up server address when
the secnond address fails.
14 41915 SNTP IP address 3, octet 2 0
15 41916 SNTP IP address 3, octet 3 0
16 41917 SNTP IP address 3, octet 4 0
17 41918 Reserved 0 0 Reserved for future use.
On a write, only a 0 is accepted. On a read, always
returns 0.
18 41919 Reserved 0 0
19 41920 Reserved 0 0