A-62 Powermonitor 3000 Data Tables
Table A.50 Event Log Text
CSP File No. N50
Remote I/O BT 37
CIP Assy. Inst. 62 (Write), 63 (Read)
No. of Elements 22
User Configurable No
Data Type Integer
Data Access Read / Write
PM3000 Type M8 only
Element
No.
Modbus
Address
Element name Range Default
Value
Comment
0 - Password 0 to 9999 0 Required for configuration, -1 for readback select,
returns -1.
1 - Write type 0 to 1 - Refer to Event Log User Comment Field (M8 only)
on page 7-6.
2 - Dnet unique write identifier -32768 to 32767 0
3 - Text block # 1 to 2 1
4 - Event record Internal identifier -1 to 32767 -
5 - User-entered timestamp; Year
Month/day
Hour/minute
Second/hsec
1998 to 2097 On a write, enter timestamp of user-entered new
event, see page 4-18.
On a read, return 0.
6 - 0101 to 1231
7 - 0000 to 2359
8 - 0000 to 5999
9- Reserved 0 0
10 - Text character pair #1 0 to 32382 -
11 - Text character pair #2
12 - Text character pair #3
13 - Text character pair #4
14 - Text character pair #5
15 - Text character pair #6
16 - Text character pair #7
17 - Text character pair #8
18 - Text character pair #9
19 - Text character pair #10
20 - Text character pair #11
21 - Text character pair #12
22 - Text character pair #13