User Manual, PRIOR to Firmware rev. 3.0 Owner manual
Publication 1404-UM001D-EN-E - October 2004
Product Description 2-11
Table 2.4 RS-232 Optional Communications (catalog numbers ending in -232)
LED LED Color LED State and Communications
Condition
F1 Off Not Used
RS-232 RX Off The RS-232 bus is idle; no active data is
present
Flashing Green Powermonitor 3000 is receiving data.
RS-232 TX Off The Powermonitor 3000 is not transmitting
any data onto the RS-232 bus
Flashing Green The Powermonitor 3000 is transmitting
data.
Table 2.5 Remote I/O Optional Communications (catalog numbers ending in -RIO)
LED LED Color LED State and Communications
Condition
F1 Off Not Used
F2 Off Not Used
R I/O Off Remote I/O communications has not been
established
Flashing Green Remote I/O communications has been
established but there are errors
Steady Green Remote I/O communications has been
established
Table 2.6 DeviceNet Optional Communications (catalog numbers ending in -DNT)
LED LED Color LED State and Communications
Condition
F1 Off Not Used
F2 Off Not Used
Network Status Off Power is off or the Powermonitor 3000 is
not online
Flashing Green Network status is OK, no connections
established
Steady Green Network status is OK, connections
established
Flashing Red Recoverable communications failure; port is
restarting
Steady Red Non-recoverable communications error;
check wiring and configuration parameters
Powermonitor 3000
F1
RX
TX
}
RS-232
Po
wermonitor 3000
wermonitor 3000
F1
F2
R I/O
Powermonitor 3000
F1
F2
NETWORK
STATUS