A-54 Powermonitor 3000 Data Tables
Table A.43 Transient Analysis Configuration/Read-Back Select
CSP File No. F43
Remote I/O BT 44
CIP Assy. Inst. 52 (Write), 53 (Read)
No. of Elements 10
User Configurable No
Data Type Floating Point
Data Access Read / Write
PM3000 Type M8 only
Applies to: Table 43: Transient analysis metering results
Element
No.
Modbus
Address
Element name Range Default
Value
Comment
0 - Password 0 to 9999 0 Required for configuration, -1 for readback select,
returns -1.
1 - DeviceNet unique write
identifier
-32768 to 32767 0 Refer to DeviceNet Unique Write Identifier on
page 4-36.
2 - Capture # 0 to 6 1 Refer to Transient Analysis Configuration on
page 8-19.
3 - Cycle # 1 to 12 1
4 - Read-back mode 0 to 1 0
5 - Detection mode 0 to 3 1
6- Reserved 0 0
7 - Auto-threshold set command 0 to 1 0
8 - Auto-threshold set duration 1 to 3600 10
9 - Auto-threshold set margin 1.0 to 100.0 20.0
10 - Voltage trigger threshold 0.1 to 100.0 10.0
11 - Current trigger threshold 0.1 to 100.0 10.0
12 - Auto-threshold duration time
left