User Manual, PRIOR to Firmware rev. 3.0 Owner manual

Publication 1404-UM001D-EN-E - October 2004
A-46 Powermonitor 3000 Data Tables
Table A.36 Harmonic Results; Odd Harmonics 23 to 41
CSP File No. F36
Remote I/O BT 40
CIP Assy. Inst. 43
No. of Elements 14
User Configurable No
Data Type Floating Point
Data Access Read only
PM3000 Type M6, M8 only
Element
No.
Modbus
Address
Element name Range Comment
0 - Channel # returned 1 to 7 Refer to Reading Harmonic Analysis Data on page 8-11
1 - Type of harmonic data returned 0 to 1
2- Reserved 0
3-
23
rd
Harmonic 0.0 to 999.9x10
22
4-
25
th
Harmonic 0.0 to 999.9x10
22
5-
27
th
Harmonic 0.0 to 999.9x10
22
6-
29
th
Harmonic 0.0 to 999.9x10
22
7-
31
st
Harmonic 0.0 to 999.9x10
22
8-
33
rd
Harmonic 0.0 to 999.9x10
22
9-
35
th
Harmonic 0.0 to 999.9x10
22
10 -
37
th
Harmonic 0.0 to 999.9x10
22
11 -
39
th
Harmonic 0.0 to 999.9x10
22
12 -
41
st
Harmonic 0.0 to 999.9x10
22
13 - FFT iteration 0 to 32767