User Manual, PRIOR to Firmware rev. 3.0 Owner manual
Publication 1404-UM001D-EN-E - October 2004
A-40 Powermonitor 3000 Data Tables
Table A.30 User-Configured Table Setup
CSP File No. N30
Remote I/O BT 35
CIP Assy. Inst. 35 (Write), 36 (Read)
No. of Elements 26
User Configurable No
Data Type Integer
Data Access Read /Write
PM3000 Type All
Applies to: Table A.31 User-Configured Table Results
Element
No.
Modbus
Address
Element name Range Default
Value
Comment
0 41101 Password 0 to 9999 0 Required for configuration, returns -1.
1 41102 DF1 File No. 31 31 Refer to User-Configured Data Table on page 4-53
Ethernet (CSP) File No. (Series A
only)
31 31
RIO BT No. 62 62
DeviceNet Ass’y Inst. 1, 37 37
EtherNet/IP (CIP) Ass’y Inst. 1, 37 37
Modbus 1000 31
2 41103 DeviceNet instance 1 data type 0 to 1 0
3 41104 Selection for parameter #1 0 to 301 71 (L1-L2 V)
4 41105 Selection for parameter #2 72 (L2-L3 V)
5 41106 Selection for parameter #3 73 (L3-L1 V)
6 41107 Selection for parameter #4 63 (I1)
7 41108 Selection for parameter #5 64 (I2)
8 41109 Selection for parameter #6 65 (I3)
9 41110 Selection for parameter #7 90 (W)
10 41111 Selection for parameter #8 98 (VA)
11 41112 Selection for parameter #9 94 (VAR)
12 41113 Selection for parameter #10 111 (PF)
13 41114 Selection for parameter #11 100 (Dmd W)
14 41115 Selection for parameter #12 122 (KWh)
15 41116 Selection for parameter #13 130 (Status)
16 41117 Selection for parameter #14 14 (Year)