User Manual, PRIOR to Firmware rev. 3.0 Owner manual
Publication 1404-UM001D-EN-E - October 2004
Powermonitor 3000 Data Tables A-39
Table A.29 List of Event Types
Applies to: Table A.27 Event Log Results
PM3000 Type See table
Event
Code.
M4
M5
M
6
M
8
Event type Event Command
Code
Comment
0 •••No event 0 The log starts with no events recorded
1 •••Setpoint triggered Setpoint Number A setpoint activated
2 •••Setpoint released A previously active setpoint released
3 •••Relay force energized Relay Number 1 = Form C relay, 2 = KYZ
4 •••Relay force de-energized
5 •••Relay force released
6 •••Status input set Status Input Number
7 •••Status input cleared
8 •••KWh counter set or cleared 1 Records command action
8 •••KVARh counter set or cleared 2
8 •••KVAh counter set or cleared 3
8 •••Ah counter set or cleared 4
8 •••All energy counters cleared 5
8 •••Trend log cleared 6
8 •••Min/max log cleared 7
8 •••Factory defaults restored 8
8 •••Status input #1 counter cleared 9
8 •••Status input #2 counter cleared 10
8 •••Reserved 11
8 •••Single setpoint timer cleared 12
8 •••All setpoint timers cleared 13
9 •••Power-up 0 Control power was applied.
10 •••Power-down 0 Control power was lost or internal reset occurred.
11 •••Selftest failure Status Error Code Refer to Table A.28 Status Error Codes (bitfield)
12 •••Date/time set 0 The date and/or time was set or altered.
13 •••Change of non-setpoint config data 0
14 •••Change of setpoint config data 0
15 •••NVRAM Clr 0 NVRAM has been cleared due to an extended loss
of control power or internal error.
16 • Transient detected
17 •
User Comment User has manually entered a comment to record the
impact of an event on your plant or process.
18 •••External Demand Sync Timeout The demand delay expired before the next expected
external demand sync
19 •••Comm Card Reset An unexpected comm card condition has been
detected and the master module has reset the
comm card in an attempt to resume normal
operation.