User Manual, PRIOR to Firmware rev. 3.0 Owner manual
Publication 1404-UM001D-EN-E - October 2004
Powermonitor 3000 Data Tables A-37
Table A.26 Event Log Configuration/Read-Back Record Select
CSP File No. N28
Remote I/O BT 9
CIP Assy. Inst. 32 (Write), 33 (Read)
No. of Elements 6
User Configurable No
Data Type Integer
Data Access Read / Write
PM3000 Type All
Applies to: Table 27: Event log results
Table 49: Event log text
Element
No.
Modbus
Address
Element name Range Default
Value
Comment
0 41001 Password 0 to 9999 0 Required for configuration, -1 for readback
select, returns -1.
1 41002 DeviceNet unique write identifier -32768 to 32767 0 Refer to DeviceNet Unique Write Identifier on
page 4-36
2 41003 Read-back mode 0 to 6 2 Refer to Configuring the Event Log Using
Communications on page 7-4
3 41004 Enable/disable logging status
input changes
0 to 1 0
4 41005 # events in the event log 1 to 50 (M4,M5)
1 to 100 (M6, M8)
-
5 41006 Enable/disable logging of
time/date set
0 to 1 1
Table A.27 Event Log Results
CSP File No. N29
Remote I/O BT 21
CIP Assy. Inst. 34
No. of Elements 14, 17 or 18 (see table)
User Configurable No
Data Type Integer
Data Access Read only
PM3000 Type See table
Element
No.
Modbus
Address
M4
M5
M
6
M
8
Element name Range Comment
0 30901 •••Reserved 0 Returns 0.
1 30902 •••Internal identifier 0 to 32768 Refer to Reading Data from the Event Log
Using Communications on page 7-5