User Manual, PRIOR to Firmware rev. 3.0 Owner manual
Publication 1404-UM001D-EN-E - October 2004
A-36 Powermonitor 3000 Data Tables
Table A.25 Min/Max Log Results
CSP File No. F27
Remote I/O BT 28
CIP Assy. Inst. 31
No. of Elements 11
User Configurable No
Data Type Floating Point
Data Access Read only
PM3000 Type All
Element
No.
Modbus
Address
Element name Range Comment
0 30801-02 Parameter # being returned 1 to 73 Refer to Reading Data from the Trend Log on page 7-12
1 30803-04 MIN value for parameter
-999.9x10
21
to 999.9x10
21
2 30805-06 MAX value for parameter
-999.9x10
21
to 999.9x10
21
3 30807-08 MIN timestamp; year
month/day
hour/minute
sec/hsec
1998 to 2097
4 30809-10 0101 to 1231
5 30811-12 0000 to 2359
6 30813-14 0000 to 5999
7 30815-16 MAX timestamp; year
month/day
hour/minute
sec/hsec
1998 to 2097
8 30817-18 0101 to 1231
9 30819-20 0000 to 2359
10 30821-22 0000 to 5999