User Manual, PRIOR to Firmware rev. 3.0 Owner manual

Publication 1404-UM001D-EN-E - October 2004
A-32 Powermonitor 3000 Data Tables
Table A.22 Trend Log Results
CSP File No. F25
Remote I/O BT 48
CIP Assy. Inst. 28
No. of Elements 14 (DeviceNet only), 22 (All other communications types)
User Configurable Yes
Data Type Floating Point
Data Access Read only
PM3000 Type All
Element
No.
Modbus
Address
Element name Range Comment
0 30701-02 Reserved 0 Returns 0
1 30703-04 Internal Identifier 0 to 15 Increment from 1 to 15 for each record, rolls to 0
2 30705-06 Timestamp; Year
Month/Date
Hour/minute
Seconds/hsec
1998 to 2097 Date and time record was recorded. Refer to Expressing Data in
Data Tables on page 4-18
3 30707-08 0101 to 1231
4 30709-10 0000 to 2359
5 30711-12 0000 to 5999
6 30713-14 User selected parameter #1 - The values of parameters that were configured.
7 30715-16 User selected parameter #2 -
8 30717-18 User selected parameter #3 -
9 30719-20 User selected parameter #4 -
10 30721-22 User selected parameter #5 -
11 30723-24 User selected parameter #6 -
12 30725-26 User selected parameter #7 -
13 30727-28 User selected parameter #8 -
14 30729-30 User selected parameter #9 -
15 30731-32 User selected parameter #10 -
16 30733-34 User selected parameter #11 -
17 30735-36 User selected parameter #12 -
18 30737-38 User selected parameter #13 -
19 30739-40 User selected parameter #14 -
20 30741-42 User selected parameter #15 -
21 30743-44 User selected parameter #16 -