User Manual, PRIOR to Firmware rev. 3.0 Owner manual

Publication 1404-UM001D-EN-E - October 2004
Powermonitor 3000 Data Tables A-27
Table A.19 List of Setpoint Types
Applies to: Refer to Table A.18 Setpoint Setup/Read-Back Select and Status
PM3000 Type See table
Param.
No.
Parameter name M4
M5
M
6
M
8
Comment
0 Not used ••Disables the setpoint.
1
Voltage
(1)
••Refer to Table A.9 Metering Voltage, Current and Frequency Result
2
Current
(1)
••
3 Voltage unbalance ••Refer to Table A.10 Metering Sequence Voltage and Current Results
4 Current unbalance ••
5 Neutral current ••
6W ••Refer to Table A.11 Metering Power Results
7VAR ••
8VA ••
9 Total true PF ••Refer to Table A.13 Metering Power Factor Results
10 Total disp PF ••
11 Total dist PF ••
12 W demand ••Refer to Table A.12 Metering Demand Results
13 VAR demand ••
14 VA demand ••
15 Amp demand ••
16 Projected amp demand ••
17 Projected W Demand ••
18 Projected VAR Demand ••
19 Projected VA Demand ••
20 Frequency ••Refer to Table A.9 Metering Voltage, Current and Frequency Result
21 Phase rotation ••Refer to Table A.10 Metering Sequence Voltage and Current Results
22 Crest factor voltage ••Refer to Table A.34 Harmonic Results; THD, Crest Factor, and More
23 Crest factor current ••
24 Crest factor I4 ••
25
IEEE THD voltage
(1)
••
26
IEEE THD current
(1)
••
27 IEEE THD I4 ••
28
IEC THD voltage
(1)
••
29
IEC THD current
(1)
••
30 IEC THD I4 ••
31 Status input 1 ••Refer to Table A.3 Discrete Data
32 Status input 2 ••
33
Any status input
(1)
••