User Manual, PRIOR to Firmware rev. 3.0 Owner manual
Publication 1404-UM001D-EN-E - October 2004
A-22 Powermonitor 3000 Data Tables
Table A.14 Metering Real and Apparent Energy Results
CSP File No. N20
Remote I/O BT 29
CIP Assy. Inst. 19 (Write), 20 (Read)
No. of Elements 23
User Configurable No
Data Type Integer
Data Access Read / Write
PM3000 Type All
Element
No.
Modbus
Address
Element Name Range Units Default
Value
Comment
0 40501 Password 0 to 9999 - 0 Required to clear or preset energy counters.
Returns -1.
1 40502 Parameter select 0 to 7
(bitfield)
- Refer to How to Clear or Preset Energy
Counters Using Communications on
page 4-52.
2 40503
KWh forward ### x 10
9
### x 10
6
### x 10
3
### x 10
0
### x 10
-3
-999 to 999 kWh
3 40504
4 40505
5 40506
6 40507
7 40508
KWh reverse ### x 10
9
### x 10
6
### x 10
3
### x 10
0
### x 10
-3
-999 to 999
8 40509
9 40510
10 40511
11 40512
12 40513
Kwh net ### x 10
9
### x 10
6
### x 10
3
### x 10
0
### x 10
-3
-999 to 999
13 40514
14 40515
15 40516
16 40517
17 40518
KVAh ### x 10
9
### x 10
6
### x 10
3
### x 10
0
### x 10-
3
-999 to 999 KVAh
18 40519
19 40520
20 40521
21 40522
22 40523 Metering iteration 0 to 32767 - Increments by 1 to 32767, rolls over to 0