User Manual, PRIOR to Firmware rev. 3.0 Owner manual

Publication 1404-UM001D-EN-E - October 2004
Powermonitor 3000 Data Tables A-21
Table A.13 Metering Power Factor Results
CSP File No. F19
Remote I/O BT 33
CIP Assy. Inst. 18
No. of Elements 13
User Configurable No
Data Type Floating point
Data Access Read only
PM3000 Type All
Element
No.
Modbus
Address
Element name Units Range Comment
0 30501-02 L1 True Power Factor Percent -100 to 100 Ratio between power and apparent power.
+ = Lead
- = Lag
1 30503-04 L2 True Power Factor -100 to 100
2 30505-06 L3 True Power Factor -100 to 100
3 30507-08 3-phase True PF -100 to 100
4 30509-10 L1 Displacement Power Factor -100 to 100 Cosine of the phase angle between the fundamental
voltage and current.
+ = Lead
- = Lag
5 30511-12 L2 Displacement Power Factor -100 to 100
6 30513-14 L3 Displacement Power Factor -100 to 100
7 30515-16 3-phase Displacement PF -100 to 100
8 30517-18 L1 Distortion Power Factor 0 to 100 The ratio between the magnitude of the fundamental
and the sum of the magnitudes for all of the current
harmonics.
9 30519-20 L2 Distortion Power Factor 0 to 100
10 30521-22 L3 Distortion Power Factor 0 to 100
11 30523-24 3-phase Distortion PF 0 to 100
12 30525-26 Metering iteration - 0 to 32767 Increments by 1 to 32767, rolls over to 0