User Manual, PRIOR to Firmware rev. 3.0 Owner manual
Publication 1404-UM001D-EN-E - October 2004
Powermonitor 3000 Data Tables A-19
Table A.11 Metering Power Results
CSP File No. F17
Remote I/O BT 31
CIP Assy. Inst. 16
No. of Elements 13
User Configurable No
Data Type Floating point
Data Access Read only
PM3000 Type All
Element
No.
Modbus
Address
Element name Units Range Comment
0 30301-02 L1 Real Power Watts (W)
0.0 to 999.9x10
22
Real power per phase, signed to show
direction.
Refer to Power Results on page 3-6.
1 30303-04 L2 Real Power
0.0 to 999.9x10
22
2 30305-06 L3 Real Power
0.0 to 999.9x10
22
3 30307-08 Total Real Power
0.0 to 999.9x10
22
Total power signed to show direction.
4 30309-10 L1 Reactive Power Volt-amps
reactive
(VAR)
0.0 to 999.9x10
22
Reactive power per phase, signed to show
direction.
5 30311-12 L2 Reactive Power
0.0 to 999.9x10
22
6 30313-14 L3 Reactive Power
0.0 to 999.9x10
22
7 30315-16 Total Reactive Power
0.0 to 999.9x10
22
Total reactive power, signed to show
direction.
8 30317-18 L1 Apparent Power Volt-amps
(VA)
0.0 to 999.9x10
22
Apparent power per phase.
9 30319-20 L2 Apparent Power
0.0 to 999.9x10
22
10 30321-22 L3 Apparent Power
0.0 to 999.9x10
22
11 30323-24 Total Apparent Power
0.0 to 999.9x10
22
Total apparent power
12 30325-26 Metering iteration - 0 to 32767 Increments by 1 to 32767, rolls over to 0