User Manual, PRIOR to Firmware rev. 3.0 Owner manual

Publication 1404-UM001D-EN-E - October 2004
Powermonitor 3000 Data Tables A-15
DeviceNet
Element
No.
Modbus
Address
Element name Range Default
Value
Comment
0 40401 Password 0 to 9999 0 Valid password required to change configuration data. Returns -1
1 40402 Node address
(MAC ID)
0 to 64 63 Address 64 enables remote node address programming; there is
no actual node address of 64 defined for DeviceNet.
2 40403 Baud rate 0 to 4 0 0 = 125k
1 = 250k
2 = 500k
3 = Auto
4 = Programmable
3 40404 Bus Off Interrupt
Action
0 to 1 0 0 = hold CAN chip in reset
1 = reset CAN chip and continue communications
4 40405 Reserved 0 0 Reserved. Must be 0 on a write, returns 0