Powermonitor 3000 Data Tables A-13
14 40415 Protocol select (ENT Series A)
Reserved (ENT Series B)
0 - 0 to 2 When master module firmware > = V1.12
& Ethernet firmware > = V2.01,
0 = CSP/CIP (concurrent support for both
protocols)
1 = CSP protocol
2 = CIP protocol
When master module firmware <V1.12 &
Ethernet firmware <V2.01, protocol
supported is CSP and this parameter is
reserved (write a 0, always reads 0).
Reserved on Series B. Must be 0 on a
write, returns 0
15 40416 Reserved 0 - 0 Reserved. Must be 0 on a write, returns 0
16 40417
17 40418
18 40419
19 40420
Ethernet
Element
No.
Modbus
Address
Element name Range Units Default
Value
Comment
ControlNet
Element
No.
Modbus
Address
Element name Range Units Default
Value
Comment
0 40401 Password 0 to 9999 - 0 Valid password required to change configuration data.
Returns -1
1 40402 MAC ID 0 to 99 - 99 On a write, sets MAC ID (node address) of
Powermonitor 3000 on ControlNet network.
2 40403 Reserved 0 - 0 Reserved. Must be 0 on a write, returns 0
3 40404
4 40405
5 40406
6 40407
7 40408
8 40409
9 40410
10 40411
11 40412
12 40413
13 40414
14 40415
15 40416
16 40417
17 40418
18 40419
19 40420