A-12 Powermonitor 3000 Data Tables
Table A.8 Optional Communication Configuration
CSP File No. N14
Remote I/O BT 24
CIP Assy. Inst. 12 (Write), 13 (Read)
No. of Elements 20
User Configurable No
Data Type Integer
Data Access Read / Write
PM3000 Type All
TIP
Select the table that applies to your Powermontior
3000.
Ethernet
Element
No.
Modbus
Address
Element name Range Units Default
Value
Comment
0 40401 Password 0 to 9999 - 0 Valid password required to change
configuration data. Returns -1
1 40402 IP address byte a 0 to 255 - 128 Format: aaa.bbb.ccc.ddd. Static IP address
of this device (for example 130.151.32.86).
Address 0.0.0.0 enables bootp server to
assign IP address, subnet mask and
gateway. If connected to a network, IP
address must be unique. (255.255.255.255
is not permitted.)
2 40403 IP address byte b 1
3 40404 IP address byte c 1
4 40405 IP address byte d Device ID Factory-assigned device ID
5 40406 Subnet mask byte a 0 to 255 - 255 Format aaa.bbb.ccc.ddd. Ignored if bootp
enabled.
6 40407 Subnet mask byte b 255
7 40408 Subnet mask byte c 255
8 40409 Subnet mask byte d 0
9 40410 Gateway IP address byte a 0 to 255 - 128 IP address of the gateway on this subnet
used to route
messages to other subnets (wide area
networking). Ignored if bootp enabled.
10 40411 Gateway IP address byte b 1
11 40412 Gateway IP address byte c 1
12 40413 Gateway IP address byte d 1
13 40414 Keep Alive Time (ENT Series A)
Reserved (ENT Series B)
0 to 3600 Seconds 30 The maximum time a socket is dedicated to
a connection that is not responding.
Reserved on Series B. Must be 0 on a
write, returns 0