User Manual, Firmware rev. 3.0 or LATER Owner's manual
Publication 1404-UM001F-EN-P - November 2009 57
Powermonitor 3000 Unit Operations Chapter 3
SNTP Address 2
The IP address of the primary SNTP server, accessed as the 1
st
…4
th
octet.
SNTP Address 3
The IP address of a third SNTP server, accessed as the 1
st
…4
th
octet.
Controller Command
The Controller Command table is a write table consisting of one
integer element. A 1 written to bit 0 signals the end of a demand
period. When this occurs, the master power monitor resets this bit to 0
and sends the end of demand broadcast to power monitor units
configured as Slave broadcast input. Bits 1…15 are reserved.
Network Demand/Time Configuration Summary
Parameter Name Range Default User Setting
Input mode
0
…3
3
Broadcast port number
300
…400
300
Time server IP address-byte 1
0
…255
0
Time server IP address-byte 2
0
…255
0
Time server IP address-byte 3
0
…255
0
Time server IP address-byte 4
0
…255
0
Time zone
-12
…12
0
Time set update interval
0
…32766
60
SNTP IP address 2, octet 1
0
…255
0
SNTP IP address 2, octet 2
0
…255
0
SNTP IP address 2, octet 3
0
…255
0
SNTP IP address 2, octet 4
0
…255
0
SNTP IP address 3, octet 1
0
…255
0
SNTP IP address 3, octet 2
0
…255
0
SNTP IP address 3, octet 3
0
…255
0
SNTP IP address 3, octet 4
0
…255
0